Form: WMS-MG331-21-VAV-WMVAVController-01D.doc Page 1 of 1
Description
The VAV/CAV Controller Board is designed with
7 usable analog inputs, 2 analog outputs and 5
relay outputs. The controllers input and output
capabilities can be expanded by use of either 2
slot or 4 slot expansion boards that plug into the
WMVAV Controller by means of a modular cable.
The WMVAV Controller can be configured for
control of VAV Units (with or without VAVBOX
Controllers), Constant Volume Units and Air to Air
Heat Pump Units. Features include the following:
Up to 8 Stages Each of Cooling and Heating
(4 on board, 12 more with expansion boards)
Selectable Control Sensor
Fan Proving Interlock
Wetbulb Control of Economizer Operation
Accepts Remote Occupied Signal
Relief Pressure Control
De-Humidification Capable
Full Economizer Control
I.A.Q. Control with C0
2
Sensor Monitoring Internal Trend Logging
7 Day, 2 Event per Day Scheduler Built In 14 Day Holiday Scheduler Built In
Optimal Start Scheduling Built In Override from Occupied to Unoccupied Mode
Supply Air Reset Capability
Accepts Remote HVAC Mode Selection
Most HVAC unit applications can be configured with the standard WMVAV Controller. If the application requires more inputs
and/or outputs, optional relay expansion boards are available from the factory to provide for additional analog, binary or digi-
tal inputs and outputs as required. These expansion boards are installed on either a 2 slot or 4 slot expansion base board
that connects to the WMVAV Controller board via a modular cable connection.
Mounting – Factory Installed
If purchased separately the WMVAV Controller is provided with an integral backplate and can be mounted in the HVAC unit
control panel or remotely located and wired to the HVAC unit.
RLY1
D1
D2D3D4D5
CX3
RAM
EPROM
C3
C2
U6
PHILIPS
CX6
C1
CX2
U2
U3
PAL
CX4
U4
TUC-5R PLUS
YS101816 REV. 2
V1
V2
V3
V5
V4
TB2
4
NETWORK
TOKEN
16
32
8
SW1
ADD
2
1
ADDRESS
V6
POWER
GND
24VAC
L1
D16
R6
C9
SC1
R11
U11
MC34064A
D13
C16
9936
VR2
7824CT
M
TB4
R27
C13
R10
VR1
C19
C18
NE5090NPB3192
0PS
U8
CX8
U9
X1
R7
D10
R13
D12
C7
CX10
U10
CX12
U12
U14
CX14
PJ3
PJ2
PJ1
EXPANSION
PRESSURE
SENSOR
T'STAT
C17
D15
R26
C20
R25
R24
R22
U15
CX13
U13
C15
R19
R15
C14
D18
D17
PU1
PU2
PU3
PU4
PU5
PU7
D6
D7
D8
D9
D11
D14
C12
C10
0-5
VDC
0-1
VDC
JP1
C11
X2
GND
TB3
INPUTS
GND
GND
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
AOUT1
AOUT2
AIN7
RN4
1
RN5
RS-485
CX5
U5
R
TB1
SHLD
T
COMM
COMM
RN3
1
RN1
U1
CX1
1
LD6
COMM
PWR
LD7
LED1
LED2
LD9
LD8
R1
U7
RV1
VREF ADJ
R28
+VREF
5.11V
TEST POINT
EWDOG
D19
RN2
1
COM1-3
COM4-5
R5
R4
R3
R2
R1
RLY2
RLY3
RLY4
RLY5
CX15
(1 MEG)
HH
P1
C21
6.2“
6.6”
7.3”
6.7”
1.1”
.20 Dia.
Typ. of 4
Technical Data MG331-21-VAV Controller
Power 24 Volt AC Weight 1.5 lb.
Power Consumption 8 VA Maximum Network Connection RS-485
Operating Temp
10°F to 149°F
Protocol HSI Open Protocol Token Passing
Operating Humidity 90% RH Non-Condensing Communications RS-485 - 9600 Baud
Inputs: Outputs:
Room Temperature Type III-10kohm sensor (1) Fan-ON/OFF
Supply Air Temperature Type III-10kohm sensor
Outside Air Temperature Type III-10kohm sensor
Static Pressure Sensor 0-5VDC
Humidity Sensor 4-20Ma
(4) User Configurable For :
Heating Or Cooling
Stages, Reversing Valve,
Warm-up Mode Box Com-
mand, Hot Gas Reheat
Control, Relief Fan Inter-
lock, Preheat Coil
(5) Relays - (2 Amp @ 24 VAC)
Remote Occupied Signal Binary Contact Economizer Analog Output 0-10 VDC
Fan Proof Of Flow Binary Contact VFD, Bypass or Inlet Vane
Control
Analog Output 0-10 VDC
Three Year Warranty WattMaster reserves the right to change specifications without notice
MG331-21-VAVCAV
WMVAV Controlle
r
Zobrazit stránku 0
1 2 3 4 5 6 ... 44 45

Shrnutí obsahu

Strany 1 - WMVAV Controlle

Form: WMS-MG331-21-VAV-WMVAVController-01D.doc Page 1 of 1DescriptionThe VAV/CAV Controller Board is designed with7 usable analog inputs, 2 analog out

Strany 2 - AVBOX Controlle

Form: WMS-StandardRoomSensor-1B.doc Page 1 of 1DescriptionThe patented design, OE21x series StandardRoom Sensor provides accurate sensing ofthe room t

Strany 3

Form: WMS-MG392-05-ModularSystemManager-1C.doc Page 1 of 1DescriptionThe MG392-05 Modular System Managerprovides a direct link to enable the systemope

Strany 4 - Modular I/O Base Board

Form: WMS-MG391-05-ModularServiceTool-1C.doc Page 1 of 1DescriptionThe MG391-05 Modular Service Toolis a system interface that provides adirect link t

Strany 5 - OE353 – 4 Slot

Form: WMS-MG364-22MiniLinkPollingDevice-1B.doc Page 1 of 1DescriptionThe MG364-22 MiniLink Polling Device isa network controller that is used to inte-

Strany 6

Form: WMS-OE361-CommLink-1B.doc Page 1 of 1DescriptionThe OE361 - CommLink II Communica-tions Interface allows user access to anycontroller connected

Strany 7 - Modular Expansion Board

Form: WMS-OE361-08-CommLinkIII-01A.doc Page 1 of 1 Description The OE361-08 CommLink III Communi-cations Interface allows computer access into th

Strany 8 - OE356 - 4 Digital Input

Form: WMS-CLKIV-SUB-01A-0907 Page 1 of 1 Description The OE361-12 CommLink IV Communi-cations Interface allows computer access into the WattMaster

Strany 9 - OE357 - 4 Relay Output

Form: WMS-OE366-USB-Link-01A.doc Page 1 of 1 Description The OE366 USB-Link allows computer access into the WattMaster VAV controls system and al

Strany 10 - Standard Room Sensors

Form: WMS-OE419-SUB-01B Page 1 of 1DescriptionThe OE419-04 Remote Link is essen-tially a 14,400 baud modem. The Re-mote Link is used for achieving rem

Strany 11 - Modular System Manage

Form: WMS-OE419-06-RemoteLnkII-01A.doc Page 1 of 1 Description The OE419-06 Remote Link II is essentially a 14,400 baud modem that connects to the

Strany 12 - Modular Service Tool

Form: WMS-MG320-VAVBOXController-1C.doc Page 1 of 1DescriptionThe MG320-00-VAV VAVBOX controller is used forcontrolling airflow and operation of VAV t

Strany 13 - MG364-22– MiniLink

Form: WMS-OE415-IP-Link Ki-1A.doc Page 1 of 1DescriptionThe OE415 IP-Link Kit is used to provideTCP/IP Internet and/or intranet connec-tion for Ethern

Strany 14 - Communications Interface

Form: WMS-OE415-02-IPModuleKit-01A.doc Page 1 of 1 Description The OE415-02 IP Module Kit (when installed and configured in the CommLink IV communi

Strany 15 - OE361-08 CommLink III

Form: WMS-OE310-21-LightingController-01A.DOC Page 1 of 1DescriptionThe OE310-21-LP Lighting Controllerallows an Orion Control System to alsocontrol t

Strany 16 - Communication Interface

Form: WMS-OE331-21-GPCPlusController-01A.doc Page 1 of 1VAV SystemDescriptionThe OE331-21 General Purpose Con-troller Plus (GPC Plus) is used for con-

Strany 17 - OE366 USB-Link

Form: WMS-OE310-21-GPC-17Controller-01A.doc Page 1 of 1DescriptionThe GPC-17 Controller is used for con-trolling equipment or processes that can-not b

Strany 18 - OE419-04 Remote Link

Form: WMS-OE331-21-KWH-Module-01A.doc Page 1 of 1 VAV System Description The OE331-21-KWH (Kilowatt Hour) Module provides the ability to record

Strany 19 - OE419-06 Remote Link II

Form: WM-OE510-RndDmpr-Sub-01A Page 1 of 2 VAV System Description The OE510-XX-VAV Pressure Depend-ent Round Damper consists of a round air dampe

Strany 20 - OE415 IP-Link Kit

Form: WM-OE510-RndDmpr-Sub-01A Page 2 of 2 VAV System Round Damper Sizing Use a load program to determine the peak load for each zone. These calc

Strany 21 - OE415-02 IP Module Kit

Form: WM-OE511-RndDmpr-Sub-01A Page 1 of 2 VAV System Description The OE511-XX-VAV Pressure Independ-ent Round Damper consists of a round air valve

Strany 22 - Mounting

Form: WM-OE511-RndDmpr-Sub-01A Page 2 of 2 VAV System Round Damper Sizing Use a load program to determine the peak load for each zone. These calcu

Strany 23 - GPC Plus Controller

Form: WMS-OE322-3Relay-1AnOutExpBrd-1C.doc Page 1 of 1 VAV System Description The OE322 - 3 Relay with Analog Out-put Expansion board is used in

Strany 24 - GPC-17 Controlle

Form: WMS-OE255-6-CO2Sensor-1B.doc Page 1 of 3DescriptionThe OE255 & OE256 CO2 Sensors areused in conjunction with various otherWattMaster contro

Strany 25 - KWH Module

Form: WMS-OE255-6-CO2Sensor-1B.doc Page 2 of 3Aspiration Box(Included & Used With OE255 Only)2-7/8''2-3/8''2-3/8''3

Strany 26 - Round Damper

Form: WMS-OE255-6-CO2Sensor-1B.doc Page 3 of 3OE255 – Duct Mounted CO2 Sensor AssemblyClear CoverSensorMounting BaseCO2 Sensor & Sub-baseAspiratio

Strany 27

Form: WMS-OE258-6-BuildingPressureSensor-1B.doc Page 1 of 1DescriptionThe OE258 Building Static Pressure Sen-sor is used to sense building pressure in

Strany 28 - Independent Round

Form: WMS-OE282-DamperActuator-1B.doc Page 1 of 1DescriptionThe OE282 Damper Actuator is a shaftmounted, floating point control actuator.Actuators ar

Strany 29 - Independent Round Damper

General NotesFILENAMEDATE:B. CREWSDESCRIPTION:PAGEDRAWN BY:Pressure Sensor1JOB NAME2.)All Wiring To Be In Accordance With Local AndNational Electrical

Strany 30 - OE255 & OE256 – CO Senso

FILENAMEDATE:B. CREWSDESCRIPTION:PAGEDRAWN BY:Duct Temperature Sensor1JOB NAME04/25/02G-DUCSENS1.CDROE230 & OE231Duct Temperature SensorsOE230 (6&

Strany 31

Notes:FILENAMEDATE:B. CREWSDESCRIPTION:PAGEDRAWN BY:Static Pressure Pickup Tube1JOB NAME04/29/02G-SPUTUBE1.CDROE290In Order To Obtain Accurate Static

Strany 32 - OE255 & OE256 – CO Senso

1.63"Notes:FILENAMEDATE:B. CREWSDESCRIPTION:PAGEDRAWN BY:Outside Air Humidity Sensor1JOB NAME4.)All Wiring To Be In Accordance WithLocal And Nati

Strany 33

Form: WMS-OE265-06-Humidistat-1A.doc Page 1 of 1VAV SystemDescriptionThe OE265-06 Wall Mounted Humidistatis used with the WMVAV controller to initi-a

Strany 34 - OE282 - Damper Actuato

Form: WMS-OE3522SlotBaseBoard-1B.doc Page 1 of 1DescriptionThe OE352 – 2 Slot Modular I/O BaseBoard is used in conjunction with the fol-lowing Modular

Strany 35 - Airflow Sensor

Form: WMS-OE265-07-Humidistat-1A.doc Page 1 of 1VAV SystemDescriptionThe OE265-07 Duct MountedHumidistat is used with theHVAC unit controller to initi

Strany 36 - Duct Temperature Sensors

8.00“0.38“Notes:FILENAMEDATE:B. CREWSDESCRIPTION:PAGEDRAWN BY:Return Air Humidity Sensor1JOB NAME4.)All Wiring To Be In Accordance WithLocal And Natio

Strany 37 - G-SPUTUBE1.CDR

3.23”1.25"Notes:FILENAMEDATE:B.CREWSDESCRIPTION:PAGEDRAWNBY:WallMountedHumiditySensor1JOBNAME2.)AllWiringToBeInAccordanceWithLocalAndNationalElec

Strany 38 - OE265-03

4.)AllWiringToBeInAccordanceWithLocalAndNationalElectricalCodesAndSpecifications.3.)GasketMustBeInstalledUnderCoverPlateToProvideRaintightSeal.Rainwat

Strany 39 - Humidistat

CONTROLSFILENAMEDATE: 01/03/05B. CREWSDESCRIPTION:PAGEDRAWN BY:G-OE233-W-TempSnsr1a.CDROE233 - Strap-On TemperatureSensor Kit Installation1JOB NAMEPla

Strany 40 - OE265-07 – Duct Mounted

4.)AllWiringToBeInAccordanceWithLocalAndNationalElectricalCodesAndSpecifications.3.)GasketMustBeInstalledUnderCoverPlateToProvideRaintightSeal.Rainwat

Strany 41 - OE265-04

Form: WMS-OE353-4SlotBaseBoard-1B.doc Page 1 of 1DescriptionThe OE353 – 4 Slot Modular I/O BaseBoard is used in conjunction with the fol-lowing Modula

Strany 42 - 1.25"

Form: WMS-OE354-4AI-1AO-ModExpBoard-1B.doc Page 1 of 1DescriptionThe OE354 - 4 Analog Input/1 AnalogOutput Modular Expansion Board is usedin conjuncti

Strany 43 - OutsideAirSensor OE250

Form: WMS-OE355-4AO-ModExpBoard-1B.doc Page 1 of 1DescriptionThe OE355 - 4 Analog Output ModularExpansion Board is used in conjunctionwith the OE352 -

Strany 44 - Sensor Kit Installation

Form: WMS-OE356-DigitalInput-ModExpBoard-1B.doc Page 1 of 1DescriptionThe OE356 - 4 Digital Input Modular Ex-pansion Board is used in conjunction with

Strany 45 - AmbientLightSensor OE259

Form: WMS-OE357-4RelayOutput-ModExpBoard-1B.doc Page 1 of 1DescriptionThe OE357 - 4 Relay Output ModularExpansion Board is used in conjunctionwith the